SAFETY CONSIDERATIONS
Due to system pressure, moving parts and electrical components,
installation and servicing of air conditioning equipment can be
hazardous. Only qualified, trained, service personnel should
install, repair, maintain or service this equipment.
‘YORK Model DCE and DCG units are single package air
conditioners designed for outdoor installation on a rooftop or a
slab and is manufactured under ISO 9002 Quality System
Certification. The DCE models are cooling only and can be
equipped with factory installed electric heaters for cooling /
heating applications. The DCG models are gas-fired central
heating furnaces with cooling.
The units are completely assembled on rigid, permanently attached
base rails. All piping, refrigerant charge, and electrical wiring is factory
installed and tested. All units require electric power, duct connections
and fixed outdoor air intake damper (units without economizer or
motorized damper option only) at the point of installation.
The DCG units additionally require gas connection, installation of the
combustion air inlet hood and the flue gas outlet hoods at the point of
installation. The gas-fired heaters have aluminized-steel tubular heat
exchangers and spark ignition with proven pilot.
Supplemental electric heaters for DCE units have nickel-chrome
elements and utilize single point power connections.
The following safety precautions apply to DCG units:
INSPECTION
As soon as a unit is received, it should be inspected for
possible damage during transit. If damage is evident, the
extent of the damage should be noted on the carrier’s freight
bill. A separate request for inspection by the carrier’s agent
should be made in writing. Refer to Form 50.15-NM for
additional information.
REFERENCE
Additional information on the design, installation, operation and
service of this equipment is available in the following reference forms:
44-320-10 - Barometric Relief Damper Accessory
530.18-N6.1V - Propane Conversion Accessory
530.18-N6.2V - High Altitude Accessory (Nat. Gas)
530.18-N6.3V - High Altitude Accessory (Propane)
530.18-n13y - Coil Guard Installation
Renewal Parts:
Refer to the Renewal Parts Manual for complete listing of
replacement parts on this equipment.
All forms referenced in this instruction may be ordered from:
Publications Distribution Center
Unitary Products Group
P.O. Box 1592, York, Pa. 17405
APPROVALS
Design certified by ETL & CGA as follows:
1. For use as a central cooling only unit with or without
supplemental electric heat. (DCE models)
2. For use as a forced air furnace with cooling unit. (DCG models)
3. For use with natural gas or propane gas. (DCG models)
4. For outdoor installation only.
5. For installation on combustible material.
®
SUNLINE 2000
ELECTRIC / ELECTRIC & GAS / ELECTRIC
SINGLE PACKAGE AIR CONDITIONERS
(Constant Air Volume)
INSTALLATION INSTRUCTION
Supersedes: 530.18-N11Y (195)
530.18-N11Y (399)
MODELS D2CE & D2CG300
(8.5 EER)
035-16133
DCG MODEL
SHOWN
208/230/460
VOLT ONLY
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make
the installation easier.
Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury
and/or equipment damage may result if installation procedure is not handled properly.
208/230/575
VOLT ONLY
CAUTION
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH
THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY
APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT
NOT LIMITED TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.
WARNING
INCORRECT INSTALLATION MAY CREATE A CONDITION
WHERE THE OPERATION OF THE PRODUCT COULD CAUSE
PERSONAL INJURY OR PROPERTY DAMAGE
FOR YOUR SAFETY
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance
.
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. Don’t touch electrical switches; do not use
any phones in the area of the gas leak.
3. Extinguish any open flame.
4. Immediately call your gas supplier from another
location. Follow your gas supplier’s
instructions.
5. If you cannot reach your gas supplier, call the
fire department.
Seitenansicht 0
1 2 3 4 5 6 ... 23 24

Inhaltsverzeichnis

Seite 1 - INSTALLATION INSTRUCTION

SAFETY CONSIDERATIONSDue to system pressure, moving parts and electrical components,installation and servicing of air conditioning equipment can behaz

Seite 2 - TABLE OF CONTENTS

TABLE 4 - PHYSICAL DATAMODELSDCE/DCG300EVAPORATORBLOWERCENTRIFUGAL BLOWER (Dia. x Wd. in.) 18 x 15FAN MOTOR HP 15EVAPORATORCOILROWS DEEP 4FINS PER INC

Seite 3 - INSTALLATION

Cont’d.FIG. 10 - DIMENSIONS & CLEARANCES - DCE & DCGAll dimensions are in inches. They are sub-ject to change without notice. Certified di-men

Seite 4 - 4 Unitary Products Group

FIG. 10 - DIMENSIONS & CLEARANCES (Cont’d.)- DCE & DCGSUPPLYAIRRETURN AIROUTDOORAIR5-1/8"18-5/8"27-3/4"29-5/8" (15 TON)39-

Seite 5 - CONTROL WIRE SIZES

ABCDFRONT 4 POINT LOADSFIG. 11- FOUR AND SIX POINT LOADSAEDBFCFRONT 6 POINT LOADSUNIT4 - POINT LOADS (LBS)TOTAL A B C D300 3,130 615 671 962 882NOTE:

Seite 6

TABLE 11 - POWER EXHAUST PERFORMANCETABLE 12 - BLOWER MOTOR AND DRIVE DATAMODELSIZEDRIVEBLOWERRANGE(RPM)MOTOR1ADJUSTABLE MOTOR PULLEY FIXED BLOWER PUL

Seite 7 - EXTERNAL SHUT-OFF

COOLING SYSTEMThe cooling section is a complete factory package utilizing anair-cooled condenser. The system is factory-charged withRefrigerant-22.The

Seite 8 - 8 Unitary Products Group

switch is in the “AUTO” position, the blower will operate onlywhen there is a call for heating by the thermostat.b) Upon a call for first-stage heat b

Seite 9 - Unitary Products Group 9

6. Auxiliary Limit Switch (AUX) This control is located insidethe heat exchanger compartment and is set to open at190°F. It is a manual reset switch.

Seite 10

3. To increase the gas pressure, turn the adjusting screwclockwise.NOTE: The correct manifold pressure for these furnaces is3.65 IWG ±0.3.PILOT CHECKO

Seite 11 - UTILITIES ENTRY DATA

2. Insert at least 8" of 1/4 inch tubing into each of these holesfor sufficient penetration into the air flow on both sides ofthe indoor coil.NOT

Seite 12 - UNIT WITH RAIN HOODS

General ... 1Inspection...

Seite 13

If the actual input is not within 5% of the furnace rating (withallowance being made for the permissible range of the regulatorsetting), replace the o

Seite 14 - Factory Setting

10. After brushing is complete, blow all brushed areas with airor nitrogen. Vacuum as needed.11. Replace parts in the order they were removed in Steps

Seite 15 - OPERATION

4. The draft motor runs but the furnace does not light and thesparker does not spark.a. The ignition control (IC1, IC2) may be locked out due toeither

Seite 16

REPLACEMENT PARTSCOMPRESSOR SECTION•Hermetic compressor•Compressor mountingMOTOR SECTION•Blower motor•Fan motor•Ventor motorELECTRICAL SECTION•Ignitio

Seite 17 - START-UP

Unitary Products Group5005 York Drive, Norman, Oklahoma 73069Subject to change without notice. Printed in U.S.A.Copyright  by York International C

Seite 18 - BURNER ASSEMBLY BRACKET

LIMITATIONSThese units must be installed in accordance with the followingapplicable national and local safety codes:In U.S.A.:1. National Electrical C

Seite 19

DUCTWORKDuctwork should be designed and sized according to themethods in Manual Q of the Air Conditioning Contractors ofAmerica (ACCA).A closed return

Seite 20 - MAINTENANCE

FIG. 5 - TYPICAL FIELD WIRINGWire Size1 AWG. Gauge22 20 19 18 1625 40 50 65 100Maximum Wire Length2 FeetNotes:1. Solid, Class II copper wireCONTROL WI

Seite 21 - TROUBLESHOOTING

THERMOSTATThe room thermostat should be located on an inside wallapproximately 56" above the floor where it will not be subjectto drafts, sun exp

Seite 22

WARNING: Natural gas may contain some propane. Propane,being an excellent solvent, will quickly dissolvewhite lead or most standard commercialcompound

Seite 23 - REPLACEMENT PARTS

VENT AND COMBUSTION AIR HOODS(DCG Models)Two vent hoods and a combustion air hood (with screens) areshipped attached to the blower housing in the blow

Seite 24

FIG. 9 - ENTHALPY SETPOINT ADJUSTMENT530.18-N11YUnitary Products Group 9