A fused disconnect switch should be field provided for the unit.
The switch must be separate from all other circuits. Wire entry
at knockout openings require conduit fittings to comply with
NEC and/or local codes. Refer to Figure 10 for installation
location. If any of the wire supplied with the unit must be
replaced, replacement wire must be of the type shown on the
wiring diagram and the same minimum gauge as the replaced
wire.
Electrical line must be sized properly to carry the load. Each
unit must be wired with a separate branch circuit fed directly
from the meter panel and properly fused.
CAUTION: When connecting electrical power and control
wiring to the unit, waterproof type connectors
MUST BE USED so that water or moisture cannot
be drawn into the unit during normal operation. The
above waterproofing conditions will also apply
when installing a field-supplied disconnect switch.
Refer to Figure 5 for typical field wiring and to the appropriate
unit wiring diagram for control circuit and power wiring
information.
COMBUSTION DISCHARGE
The products of combustion are discharged horizontally
through two screened (hooded) openings on the upper gas
heat access panel.
GAS PIPING
Proper sizing of gas piping depends on the cubic feet per hour
of gas flow required, specific gravity of the gas and the length
of run.National Fuel Gas Code” Z223.1 should be followed in
all cases unless superseded by local codes or gas utility
requirements. Refer to Table 5.
The heating value of the gas may differ with locality. The value
should be checked with the local gas utility.
NOTE: There may be a local gas utility requirement specifying
a minimum diameter for gas piping. All units require a
1 inch pipe connection at the entrance fitting.
FIG. 5 - TYPICAL FIELD WIRING
Input Capacity (Mbh) Output Capacity (Mbh)
Available
on Models
Gas
Rate
2
(Ft.
3
/Hr.)
Te mp.
Rise ÉF
At
Full Input
3
0 To
2,000 Feet
Above
Sea Level
2,000 To
4,500 Feet
Above
Sea Level
1
0 To
2,000 Feet
Above
Sea Level
2,000 To
4,500 Feet
Above
Sea Level
1
Max. Min. Max. Min. Max. Max. Min. Max.
300 150 270 135 240 213 15 & 20 Ton 279 20 50
400 200 360 180 320 281 15 & 20 Ton 372 30 60
NOTE: Heaters are shipped available for natural gas, but can be converted to
L.P. / Propane with Kit Model No. 1NP0418.
1
MBH rating should be reduced at the rate of 4 percent for each 1,000 feet above 4,500 feet.
2
Based on maximum input and 1075 Btu/Ft
3
.
3
The air flow must be adjusted to obtain a temperature rise within the range shown.
TABLE 2 - GAS HEAT APPLICATION DATA
Length in Feet
Nominal Iron Pipe Size
1 in. 1-1/4 in.
10
20
30
40
50
60
70
80
90
100
520
350
285
245
215
195
180
170
160
150
1,050
730
590
500
440
400
370
350
320
305
Maximum capacity of pipe in cubic feet of gas per hour. (Based upon a pressure drop of 0.3
inch water column and 0.6 specific gravity gas).
TABLE 4 - PIPE SIZING
Wire Size
1
AWG. Gauge
22 20 19 18 16
40 120 150 190 305
Maximum Wire Length
2
Feet
Notes:
1. Solid, Class II copper wire
TABLE 3 - CONTROL WIRE SIZES
530.22-N6Y
Unitary Products Group 5