406905-UIM-C-1009
R-410A
HORIZONTAL DISCHARGE
AIR CONDITIONING
MODELS: 13 SEER
YCHD/TCHD SERIES
1.5 TO 5 TONS – 1 & 3 PHASE
INSTALLATION MANUAL
LISTED
ISO 9001
Certified Quality
Management System
LIST OF SECTIONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
TXV INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
LIST OF FIGURES
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation of Vapor Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Outdoor Unit Field Wiring Control Box . . . . . . . . . . . . . . . . . . . . . . . . .6
Typical Field Wiring (Air Handler / Electrical Heat) . . . . . . . . . . . . . . .7
Thermostat Chart - Single Stage AC with PSC Air Handler . . . . . . . . 8
Thermostat Chart - Single Stage AC with PSC Air Handler . . . . . . . . 9
Thermostat Chart - Single Stage AC with PSC Furnace . . . . . . . . . 10
Thermostat Chart - Single Stage AC with PSC Furnace . . . . . . . . . 11
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
LIST OF TABLES
Application Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for a matching indoor coil plus 15 feet of field supplied
lines.
The refrigerant charge may need to be changed for some indoor-out-
door unit combinations, elevation differences or total line lengths. Refer
to Application Data covering “General Piping Recommendations and
Refrigerant Line Length” (Part Number 247077).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury
.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury
.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury
. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s delivery receipt. A separate request for
inspection by the carrier’s agent should be made in writing. See Local
Distributor for more information.
Requirements For Installing/Servicing R-410A Equipment
Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle the POE type oils, and the higher
pressures of R-410A.
Manifold sets should be 800 PSIG high side and 250 PSIG low
side with 550 PSIG low side retard.
All hoses must have a 700 PSIG service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
Recovery equipment (including refrigerant recovery containers)
must be specifically designed to handle R-410A.
Do not use an R-22 TXV.
A liquid-line filter drier is required on every unit.
This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
R-410A systems operate at higher pressures than R-22 systems.
Do not use R-22 service equipment or components on R-410A
equipment. Service equipment
Must Be Rated for R-410A.
Seitenansicht 0
1 2 3 4 5 6 ... 15 16

Inhaltsverzeichnis

Seite 1 - INSTALLATION MANUAL

406905-UIM-C-1009R-410AHORIZONTAL DISCHARGE AIR CONDITIONINGMODELS: 13 SEERYCHD/TCHD SERIES1.5 TO 5 TONS – 1 & 3 PHASEINSTALLATION MANUALLISTEDISO

Seite 2 - ADD-ON REPLACEMENT/RETROFIT

406905-UIM-C-100910 Johnson Controls Unitary Products FIGURE 10: Thermostat Chart - Single Stage AC with PSC FurnaceAC 5D Single Stage Air Conditione

Seite 3

406905-UIM-C-1009Johnson Controls Unitary Products 11 FIGURE 11: Thermostat Chart - Single Stage AC with PSC FurnaceAC 5E Single Stage Air Conditione

Seite 4

406905-UIM-C-100912 Johnson Controls Unitary ProductsSECTION VIII: INSTRUCTING THE OWNERAssist owner with processing warranty cards and/or online regi

Seite 5 - SECTION VI: SYSTEM CHARGE

406905-UIM-C-1009Johnson Controls Unitary Products 13SECTION IX: WIRING DIAGRAM FIGURE 12: Wiring Diagram (Single-Phase)*400975*

Seite 6 - CONNECTIONS

406905-UIM-C-100914 Johnson Controls Unitary Products FIGURE 13: Wiring Diagram (Three-Phase)

Seite 7

406905-UIM-C-1009Johnson Controls Unitary Products 15NOTES

Seite 8

Subject to change without notice. Published in U.S.A. 406905-UIM-C-1009Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: 406

Seite 9

406905-UIM-C-10092 Johnson Controls Unitary ProductsLIMITATIONSThe unit should be installed in accordance with all National, State andLocal Safety Cod

Seite 10 - 406905-UIM-C-1009

406905-UIM-C-1009Johnson Controls Unitary Products 3GROUND INSTALLATIONThe unit should be installed on a solid base that is 2” above grade andwill not

Seite 11

406905-UIM-C-10094 Johnson Controls Unitary ProductsPRECAUTIONS DURING BRAZING OF LINESAll outdoor unit and evaporator coil connections are copper-to-

Seite 12 - MAINTENANCE

406905-UIM-C-1009Johnson Controls Unitary Products 512. Release the refrigerant charge into the system. Open both the liq-uid and vapor valves by remo

Seite 13 - *400975*

406905-UIM-C-10096 Johnson Controls Unitary ProductsSUBCOOLING CHARGING METHOD - TXV INDOORFor cooling operation, the subcooling values are shown in p

Seite 14

406905-UIM-C-1009Johnson Controls Unitary Products 7FIELD CONNECTIONS CONTROL WIRING1. Route low voltage wiring into bottom of field wiring box as sho

Seite 15

406905-UIM-C-10098 Johnson Controls Unitary ProductsFor additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” docu

Seite 16 - Norman, OK 73069

406905-UIM-C-1009Johnson Controls Unitary Products 9 FIGURE 9: Thermostat Chart - Single Stage AC with PSC Air HandlerAC 1B Single Stage Air Conditio