Unitary Products Group 7
POWER WIRING
ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60
Model
Heater
Model
Min. Circuit Ampacity
Max. O.C.P.
1
Amps/Type
75°C Wire Size - AWG
Circuit Circuit Circuit
1st 2nd 3rd 1st 2nd 3rd 1st 2nd 3rd
208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240
MV12B 4HK165N1506 49.2 / 55.4 21.7 / 25.0 50 / 60 25 / 25 8 / 6 10 / 10
MV12D
4HK16501506 49.2 / 55.4 21.7 / 25.0 50 / 60 25 / 25 8 / 6 10 / 10
4HK16501806 45.6 / 51.2 39.7 / 45.8 50 / 60 40 / 50 8 / 6 8 / 8
4HK16502006 49.2 / 55.4 43.3 / 50.0 50 / 60 45 / 50 8 / 6 8 / 8
MV16C
4HK16501506 51.0 / 56.9 21.7 / 25.0 50 / 60 25 / 25 8 / 6 10 / 10
4HK16501806 17.3 / 52.7 39.7 / 45.8 50 / 60 40 / 50 8 / 6 8 / 8
4HK16502006 51.0 / 56.9 43.3 / 50.0 50 / 60 45 / 50 8 / 6 8 / 8
MV20D
4HK16501506 53.1 / 58.8 21.7 / 25.0 60 / 60 25 / 25 6 / 6 10 / 10
4HK16501806 49.5 / 54.6 39.7 / 45.8 50 / 60 40 / 50 8 / 6 8 / 8
4HK16502006 53.1 / 58.8 43.3 / 50.0 60 / 60 45 / 50 6 / 6 8 / 8
4HK16502506 49.3 / 56.5 43.3 / 50.0 21.7 / 25.0 50 / 60 45 / 50 25 / 25 8 / 6 8 / 8 10 / 10
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
KW & MBH CONVERSIONS
FOR
208-VOLT
OPERATION MULTIPLY
240-VOLT
TABULATED KW & MBH BY
.751
230-VOLT 240-VOLT .918
ELECTRICAL DATA - COOLING UNIT ONLY (60 Hz)
MODEL
Total Motor Amps Minimum Circuit Ampacity
Max. O.C.P.
1
Amps/Type
Minimum Wire Size
AWG @ 75°C
60 Hertz 60 Hertz
208V 230V 208V 230V
MV12B 4.7 4.3 5.9 5.4 15 14
MV12D 4.7 4.3 5.9 5.4 15 14
MV16C 6.1 5.0 7.6 6.9 15 14
MV20D 7.8 7.0 9.7 8.8 15 14
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
Line Power
ELECTRIC HEAT
WITHOUT CIRCUIT BREAKER
SINGLE SOURCE (2.5 - 10 KW)
GND. LUG
POWER
SUPPLY
GND.
LUG
ELECTRIC HEAT
WITHOUT CIRCUIT BREAKER
3 PHASE (10 - 15 KW)
GND. LUG
POWER
SUPPLY
GND.
LUG
1 PHASE ELECTRIC HEAT
WITH CIRCUIT BREAKER
AS SHIPPED FROM FACTORY
SINGLE SOURCE
(2.5 - 25 KW) - 25 KW SHOWN
GND. LUG
POWER
SUPPLY
GND.
LUG
1 PHASE ELECTRIC HEAT
WITH CIRCUIT BREAKER
& BREAKER BAR REMOVED
MULTI-SOURCE (15 - 25 KW) - 25 KW SHOWN
GND. LUG
POWER
SUPPLY 1
GND.
LUG
POWER
SUPPLY 2
POWER
SUPPLY 3
TYPICAL WIRING WITHOUT ELECTRIC HEAT
GND. LUG
POWER
SUPPLY
GND.
LUG
POWER WIRING (208/230-1-60)
NOTE: USE ONLY COPPER CONDUCTORS
TERMINAL
BLOCK
TERMINAL
BLOCK
MAYBE1,2,OR3
CIRCUIT BREAKERS
MAYBE1,2,OR3
CIRCUIT BREAKERS
(JUMPER BAR)
CONNECT LEADS WITH WIRE NUTS
(TYPICAL ALL HEAT KITS)